Product Description
Operation
Maniks pulse valves are operated by integral solenoid pilot operator. When the valve is energized, the trapped air above pulse valve diaphragm is quickly exhausted causing fast opening of main diaphragm valve, air escapes through bleed hole of main pulse valve to balance the diaphragm pressure and instantly closes the valve.
Duty cycle
The relative duty time cycle for AC Voltage is 20% and for DC 10% . This implies energized time is maximum 1/5 th of de-energised time for AC and 1/10 th for DC.
Installation
Mounting in any position will not affect operation of the pulse valve. However good engineering practice is to avoid scale and condensed water entering the valve body for trouble free performance. Standard end connections of BSP are provided.
Specifications:
Electrical standard voltage
AC 50 Hz 24/110/220 Volts
DC 24/110 Volts
Fluctuation 10 %
Power Consumption
31 W DC Current
14 VA AC Current
Temperature Range
Maximum Medium temperature 85°C
Maximum Ambient temperature 55°C
Dimension Table